Products

Product Details

Mecer 3000VA/2400W Smart Online UPS (ME-3000-WPTU)

PART CODE : ME-3000-WPTU
STOCK : Ex -stock
KES 126,045.77 ( KES 108,660.15 Excl VAT)

Mecer 3000VA/2400W ACCESSORY AS THE BELOW W/ 12V9AH BATTERY*6PCS, W/ RS232 PORT, W/ RS232 CABLE,w/USB port,w/SNMP slot,w/USB cable, W/ IEC SOCKET* 4PCS+TB*1, W/ UK INPUT POWERCORD* 1 PC, W/ IEC O/P POWERCORD* 1 PC, W/ CD ROM

Attribute Value
SIZE 3000VA
TYPE Smart Online UPS
WEIGHT 28.8kg
DIMENSION 426 x 190 x 318mm

Buy Now

Product Details

SPECIFICATIONS

Model

ME-3000-WPTU

Capacity

3000 VA / 2400 W

Voltage Range

Low Line Transfer

160/140/120/110 VAC ± 5% or 80/70/60/50 VAC ± 5% (based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)

Low Line Comeback

168/148/128/118 VAC ± 5% or 84VAC/74/64/54 VAC ± 5% (based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)

Low Line Comeback (Auto Restart)

168 VAC ± 5% or 84 VAC ± 5% (80% - 100% Load)

148 VAC ± 5% or 74 VAC ± 5% (0% - 80% Load)

High Line Transfer

300 VAC ± 5% or 150 VAC ± 5%

High Line Comeback

290 VAC ± 5% or 145 VAC ± 5%

Frequency Range

40 - 70Hz (Auto Sensing)

Phase

Single phase with ground

Power Factor (Nominal Output At Full Load)

More than 0.98

Output

Output Voltage

208/220/230/240 VAC or 110/115/120/127 VAC

AC Voltage Regulation (Batt. Mode)

± 1%

Frequency Range (Synchronized Range)

47 - 53Hz or 57 - 63Hz

Current Crest Ratio

3:1

Harmonic Distortion

More than 4% THD (Linear Load)

Less than 7% THD (Non-linear Load)

Transfer Time

AC Mode to Batt. Mode

Zero

Inverter to Bypass

4ms (Typical)

Waveform (Batt. Mode)

Pure Sinewave

Efficiency (Peak)

AC Mode (At 100% RCD Load)

87%

Battery Mode (At 100% RCD Load)

85%

Battery

Battery Type

12V / 9Ah

Battery Numbers

6

Charging Current

1.0 A

Charging Voltage

82.1 VDC ± 1%

Indicators

LCD Panel

UPS status, Load level, Battery level, Input/Output voltage, Discharge timer and Fault conditions

Alarm

Battery Mode (At 100% RCD Load)

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

Sounding twice every second

Fault

Continuosly sounding

Dimension (DxWxH)

426 x 190 x 318mm

Net Weight

28.8kg

Environment

Noise Level

Less than 45dB at 1 Meter

Management

Communication

USB Card / Optional RS-232 Card, SNMP Card or AS-400 Card available

Supports Windows 2000 / 2003 / XP / Vista / 2008, Windows 7, Linux, Unix and MAC

Optional SNMP

Power management from SNMP manager and web browser

 

 

Worth Checking